LS TYPE

  • Permanent installation
  • Automatic Loading & Maintaining Generators

SEPHCO LS Series Resistive-Automatic Load Banks

For Permanent Installation, designed and equipped with Smartload automatic load control system with intelligent software to maintain generator/s at a constant set load, eliminating wet stacking and cylinder glazing. LS series are also available for regenerative power applications as referred to models LS-RG.

SEPHCO LS SERIES RESISTIVE LOAD BANKS

Series LS2V, LS4V, LS6V, LS12V, LS18V, LS24V From 150kW to 2500kW Models

SEPHCO LS SERIES RESISTIVE LOAD BANKS
FEATURES
  • Weatherproof to IP54 (NEMA3S)
  • Vertical Air Discharge
  • Compact Design
  • Integrated Control System With Optional Manual Override
  • Modbus Interface Available As An Option
  • Corrosion Resistant Marine Acrylic Finish
  • Stainless Steel Vibration & Immersion Proof Resistors
  • Compact Design
APPLICATIONS
  • Prime Power Generators
  • Data Centres
  • Office Buildings
  • Telecommunication Sites
  • Essential Services
  • Mining
  • Military Establishments
  • Pumping Application

LS Series Description

LS series load banks are designed for permanent installation suitable for harsh outdoor environments. Featuring the Smartload LSM800MB processor, providing accurate load control with incremental load steps to maintain generators at a constant set load, eliminating wet stacking and cylinder bore glazing.

The control software is designed to load and maintain one or more generators, typically a single generator operation or when in parallel. The LSM800MB provides user-friendly field settings, digital display and is available with options to include a remote manual override “Mimic” control panel with Auto Exercising function and Modbus interface. For regenerative applications, units are available with the LSM800MB-RG regenerative control system.

Sephco load banks incorporate immersion proof and vibration proof stainless steel resistors. Safety features include the Sephco “Triple Interlock” load protection system, guarding against fan cooling failure, airflow restriction, high temperature and fan reversal. Unique features of Sephco load banks include circuit breaker protection for each load group and full accessibility to switchgear components and resistors.

Installation of LS type load banks will ensure optimum reliable power from generators. Constant load maintained on generators will prevent wet stacking, cylinder bore glazing and reduce emissions.

Controls

Detailed description, technical data, control type and options are available here.

LSM800MB Automatic Generator Load Controllers

The LSM800MB load bank controller is a monitoring processor which monitors the plant or building load on generators. To maintain the generator at a desired load set by the controller, loads from the load bank are automatically applied as the building or plant load varies. Loads are applied in discreet values to prevent transient conditions on the generator. Fitted with dual menus as an option, the controller expands the monitoring operation to load a two-generator operation.

The controller and load bank is activated only when a voltage-free signal is applied.

All settings such as generator capacity, CT value, operating voltage and time delay are field adjustable. Settings remain in memory even during power loss.

Generator Monitoring Input Options

Options of system monitoring inputs are available typically
1. 0-5 Amps (CT) Standard 2. 0-10 VDC (0V=Zero Generator Amps, 10V=Full Generator Amps)

External Command Input

1. External Command Using 0-10VDC (0V=Zero Generator Amps, 10V=Full Generator Amps) Load steps regulated by external PLC.

The monitoring of the load bank’s safety interlocks and fan cooling is still maintained and managed by the LSM800MB controller.

LS800MPE Manual Override “MIMIC” Control Pane

The LS800MPE is an optional control panel added to the load bank installation for remote, manual override of the load bank for periodical testing and exercising of the generator. Connection is by a simple three-core cable, connected to the load bank’s auxiliary terminals. Featuring a touch-type keypad and LED display, the LS800MPE offers simple operation for manual controllability of the load bank.

Selection of operation includes Manual Loading, Auto-Loading and Auto Genset Exercise modes. The exercising function is programmable by setting up a load routine with time duration. The LED display indicates the kilowatt value activated at the load bank during any of the switching operations. Additional LED’s display mode selection and the status of the load bank, including fan-cooling fault.

The remote “Enable” signal connected to the LSM800MB prevents operation of the Mimic panel when the generating system is operating in the emergency back-up mode, preventing inadvertent use of the load bank. When the “Enable” signal is closed, the control system reverts back to auto-loading of the generator.

SEPHCO LS Series Load Bank Dimensions

LS0V SERIES 20kW To 125kW
resistive automatic load banks 20kw-125kw
LSM800MB
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
WEIGHT
NOISE LEVEL

LS0V125

125KW

25KW

745

835

985

156 KG

78dBa @ 1M

LS0V100

100KW

10KW

745

835

985

156 KG

78dBa @ 1M

LS0V75

75KW

10KW

745

835

985

145 KG

69dBa @ 1M

LS0V60

60KW

15KW

745

835

985

135 KG

69dBa @ 1M

LS0V50

50KW

10KW

745

835

985

135 KG

69dBa @ 1M

LS0V40

40KW

10KW

745

835

985

130 KG

69dBa @ 1M

LS0V30

30KW

5KW

745

835

985

130 KG

69dBa @ 1M

LS0V25

25KW

5KW

745

835

985

125 KG

69dBa @ 1M

LS0V20

20KW

5KW

745

835

985

125 KG

69dBa @ 1M

LS2V, LS4V, LS6V SERIES 150kW To 600kW
LSM800MB
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT

LS6V600

600KW

50KW

1405

1310

1720

9.0 cu.m/s

88.0dBA @1M

650 KG

LS6V500

500KW

50KW

1405

1310

1720

9.0 cu.m/s

88.0dBA @1M

600 KG

LS4V400

400KW

40KW

1305

1175

1510

6.6 cu.m/s

80.5dBA @1M

450 KG

LS4V360

360KW

40KW

1305

1175

1510

6.6 cu.m/s

80.5dBA @1M

425 KG

LS4V320

320KW

40KW

1305

1175

1510

6.6 cu.m/s

80.5dBA @1M

400 KG

LS4V280

280KW

40KW

1305

1175

1510

6.6 cu.m/s

80.5dBA @1M

375 KG.

LS4V240

240KW

40KW

1305

1175

1510

6.6 cu.m/s

80.5dBA @1M

345 KG

LS2V200

200KW

25KW

1105

975

1400

4.7 cu.m/s

72 dBA @1M

320 KG

LS2V150

150KW

25KW

1105

975

1400

4.7 cu.m/s

72 dBA @1M

300 KG

LS12V SERIES 800kW to 1200kW
LSM800MB
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT

LS12V1200

1200KW

50KW

2405

1310

1865

17.9 cu.m/s

91 dBA @1M

1200 KG

LS12V1000

1000KW

50KW

2405

1310

1865

17.9 cu.m/s

91 dBA @1M

1000 KG

LS12V800

800KW

50KW

2405

1310

1865

17.9 cu.m/s

91 dBA @1M

946 KG

LS18V SERIES 1500kW to 2000kW
LSM800MB
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT

LS18V2000

2000KW

50KW

3405

1310

1760

26.9 cu.m/s

92 dBA @1M

1940 KG

LS18V1800

1800KW

50KW

3405

1310

1760

26.9 cu.m/s

92 dBA @1M

1900 KG

LS18V1500

1500KW

50KW

3405

1310

1760

26.9 cu.m/s

92 dBA @1M

1800 KG

LS24V SERIES 2200kW to 2500kW
resistive automatic load banks 2200kw-2500kw
LSM800MB
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT

LS24V2500

2500KW

50KW

4405

1310

1760

35.9 cu.m/s

93.5 dBA @1M

2350 KG

LS24V2400

2400KW

50KW

4405

1310

1760

35.9 cu.m/s

93.5 dBA @1M

2300 KG

LS24V2200

2200KW

50KW

4405

1310

1760

35.9 cu.m/s

93.5 dBA @1M

2250 KG

Options & Accessories

For Permanent Installation To Periodically Test & Exercise Stand-By Generators & UPS Systems. Weatherproof Construction, Complete With Controls.

LSM800MB Automatic Generator Load Controllers

The LSM800MB load bank controller is a monitoring processor which monitors the plant or building load on generators. To maintain the generator at a desired load set by the controller, loads from the load bank are automatically applied as the building or plant load varies. Loads are applied in discreet values to prevent transient conditions on the generator. Fitted with dual menus as an option, the controller expands the monitoring operation to load a two-generator operation.

The controller and load bank is activated only when a voltage-free signal is applied.

All settings such as generator capacity, CT value, operating voltage and time delay are field adjustable. Settings remain in memory even during power loss.

lscontrolnew

Generator Monitoring Input Options

Options of system monitoring inputs are available typically

  • 0-5 Amps (CT) Standard
  • 0-10 VDC (0V=Zero Generator Amps, 10V=Full Generator Amps)

External Command Input

  • External Command Using 0-10VDC (0V=Zero Generator Amps, 10V=Full Generator Amps) Load steps regulated by external PLC.

The monitoring of the load bank’s safety interlocks and fan cooling is still maintained and managed by the LSM800MB controller.

LS800MPE Manual Override “MIMIC” Control Panel

The LS800MPE is an optional control panel added to the load bank installation for remote, manual override of the load bank for periodical testing and exercising of the generator. Connection is by a simple three-core cable, connected to the load bank’s auxiliary terminals. Featuring a touch-type keypad and LED display, the LS800MPE offers simple operation for manual controllability of the load bank.

Selection of operation includes Manual Loading, Auto-Loading and Auto Genset Exercise modes. The exercising function is programmable by setting up a load routine with time duration. The LED display indicates the kilowatt value activated at the load bank during any of the switching operations. Additional LED’s display mode selection and the status of the load bank, including fan-cooling fault.

The remote “Enable” signal connected to the LSM800MB prevents operation of the Mimic panel when the generating system is operating in the emergency back-up mode, preventing inadvertent use of the load bank. When the “Enable” signal is closed, the control system reverts back to auto-loading of the generator.

ls2

LSM800MB

ls2

LS800MPE

Engineers Submittal Specifications

For Permanent Installation To Periodically Test & Exercise Stand-By Generators & UPS Systems. Weatherproof Construction, Complete With Controls.

(AU Callers)