- Permanent Installation
- Testing and Exercising of Generators
SEPHCO BL Series Resistive Load Banks
For Permanent Installation To Periodically Test & Exercise Stand-By Generators & UPS Systems. Weatherproof Construction, Complete With Controls.
Series BL2V, BL4V, BL6V, BL12V, BL18V, BL24V From 150kW to 2500kW Models
- Weatherproof to IP54 (NEMA3S)
- Vertical Air Discharge
- Compact Design
- Integrated Control System, Remote Or Local
- Modbus Interface Available As An Option
- Corrosion Resistant Marine Acrylic Finish
- Stainless Steel Vibration & Immersion Proof Resistors
- Optional stainless steel construction
- Data Centres
- Hospitals
- Office Buildings
- Telecommunication Sites
- Essential Services
- Mining
- Military Establishments
- Mining
BL Series Description
BL series load banks are designed for permanent installation, suitable for harsh outdoor environments. Control arrangement and type is specifically designed for testing and exercising stand-by generators and UPS systems.Sephco load banks incorporate immersion proof and vibration proof stainless steel resistors.
Safety features include the Sephco “Triple Interlock” load protection system, guarding against fan cooling failure, airflow restriction, high temperature and fan reversal. Unique features of Sephco load banks include circuit breaker protection for each load group and full accessibility to switchgear components and resistors.
Installation of BL type load banks will ensure reliable back-up power from generators. Frequent exercising of generators will prevent wet stacking, cylinder bore glazing and reduce emissions.
Controls
BL series load banks are supplied with full control facility, locally fitted to the load bank or supplied loose for remote control. Additional options include Modbus interface.
RTSW Control For BL Series Load Banks 25kW To 125kW
BL0V….RTSW Style Load Banks from 25kW to 125kW capacities are fitted with a weatherproof rotary type selector switch for manual control of the load bank. The switch operation features fan-start and load step increments. A fan cool-down function is automatically activated when the load bank is shut down. Auxiliary terminals are included in the load bank connections for a remote dump function.
MC12PMB Control For BL Series Load Banks
The MC12PMB control panel is standard on all models from 150kW and higher. The control panel is supplied as an option on BL0V type load banks ranging from 25kW to125kW capacities.
The MC12PMB controller is generally supplied loose for remote mounting however, can be supplied fitted to the load bank if required. The control panel features a touch type keypad and LED load display, with simple operation of the load bank start up, kilowatt selection and load bank status.
The unit automatically configures the load steps in the load bank to provide instant kilowatt response as selected by the Up/Down keys. Other features include load bank “system check” which prevents loading in the event of fan cooling failure, fan reversal or high temperature. The control has additional inputs for a remote “Enable-Disable” signal andoptional Modbus interface.
OPERATING FEATURES
- Digital kilowatt display of load value
- Touch key button operation
- Fan “Start”-“Stop” buttons
- Kilowatt “UP” – “Down” buttons
- Enter (Master) button
- Emergency “Stop” button
- LED Display:-
- LED – Load Bank “ON” indication
LED – Load Bank “COOLING FAULT” indication - LED – Load Bank “FAN RUN-ON” indication
- LED – Modbus Active
- LED – Modbus Running
- Remote-Automatic Load Dump contact facility
- Outputs to indicate load bank “Operating Normally”
- and “Load Bank Failure”.
SEPHCO BL Series Resistive Load Banks
RTSW Series – Rotary load selector switch Mounted on side of load bank
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
WEIGHT
NOISE LEVEL
BL0V125RTSW
125KW
25KW
745
835
985
156 KG
78dBa @ 1M
BL0V100RTSW
100KW
10KW
745
835
985
156 KG
78dBa @ 1M
BL0V75RTSW
75KW
10KW
745
835
985
145 KG
69dBa @ 1M
BL0V60RTSW
60KW
15KW
745
835
985
135 KG
69dBa @ 1M
BL0V50RTSW
50KW
10KW
745
835
985
135 KG
69dBa @ 1M
BL0V40RTSW
40KW
10KW
745
835
985
130 KG
69dBa @ 1M
BL0V30RTSW
30KW
5KW
745
835
985
130 KG
69dBa @ 1M
BL0V25RTSW
25KW
5KW
745
835
985
125 KG
69dBa @ 1M
BL0V20RTSW
20KW
5KW
745
835
985
125 KG
69dBa @ 1M
MC Series – Digital touch load selection control panelMC-P for remote mounting
MC-L Fitted to Load Bank
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
WEIGHT
NOISE LEVEL
BL0V125MC
125KW
25KW
745
835
985
156 KG
78dBa @ 1M
BL0V100MC
100KW
10KW
745
835
985
156 KG
78dBa @ 1M
BL0V75MC
75KW
10KW
745
835
985
145 KG
69dBa @ 1M
BL0V60MC
60KW
15KW
745
835
985
135 KG
69dBa @ 1M
BL0V50MC
50KW
10KW
745
830
985
135 KG
69dBa @ 1M
BL0V40MC
40KW
10KW
745
835
985
130 KG
69dBa @ 1M
BL0V30MC
30KW
5KW
745
835
985
130 KG
69dBa @ 1M
BL0V25MC
25KW
5KW
745
835
985
125 KG
69dBa @ 1M
BL0V20MC
20KW
5KW
745
835
985
125 KG
69dBa @ 1M
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT
BL6V600MC
600KW
50KW
1405
1310
1720
9.0 cu.m/s
88.0dBA @1M
650 KG
BL6V500MC
500KW
50KW
1405
1310
1720
9.0 cu.m/s
88.0dBA @1M
600 KG
BL4V400MC
400KW
40KW
1305
1175
1510
6.6 cu.m/s
80.5dBA @1M
450 KG
BL4V360MC
360KW
40KW
1305
1175
1510
6.6 cu.m/s
80.5dBA @1M
425 KG
BL4V320MC
320KW
40KW
1305
1175
1510
6.6 cu.m/s
80.5dBA @1M
400 KG
BL4V280MC
280KW
40KW
1305
1175
1510
6.6 cu.m/s
80.5dBA @1M
375 KG.
BL4V240MC
240KW
40KW
1305
1175
1510
6.6 cu.m/s
80.5dBA @1M
345 KG
BL2V200MC
200KW
25KW
1105
975
1400
4.7 cu.m/s
72 dBA @1M
320 KG
BL2V150MC
150KW
25KW
1105
975
1400
4.7 cu.m/s
72 dBA @1M
300 KG
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT
BL12V1200MC
1200KW
50KW
2405
1310
1865
17.9 cu.m/s
91 dBA @1M
1200 KG
BL12V1000MC
1000KW
50KW
2405
1310
1865
17.9 cu.m/s
91 dBA @1M
1000 KG
BL12V800MC
800KW
50KW
2405
1310
1865
17.9 cu.m/s
91 dBA @1M
1000 KG
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT
BL18V2000MC
2000KW
50KW
3405
1310
1760
26.9 cu.m/s
92 dBA @1M
1940 KG
BL18V1800MC
1800KW
50KW
3405
1310
1760
26.9 cu.m/s
92 dBA @1M
1900 KG
BL18V1500MC
1500KW
50KW
3405
1310
1760
26.9 cu.m/s
92 dBA @1M
1800 KG
MODEL No
RATING
LOAD STEPS
DIM.A
DIM.B
DIM.C
AIR DISCHARGE
NOISE LEVEL
WEIGHT
BL24V2500MC
2500KW
50KW
4405
1310
1760
35.9 cu.m/s
93.5 dBA @1M
2350 KG
BL24V2400MC
2400KW
50KW
4405
1310
1760
35.9 cu.m/s
93.5 dBA @1M
2300 KG
BL24V2200MC
2200KW
50KW
4405
1310
1760
35.9 cu.m/s
93.5 dBA @1M
2250 KG
Operation & Accessories
For Permanent Installation To Periodically Test & Exercise Stand-By Generators & UPS Systems. Weatherproof Construction, Complete With Controls.
TYPE RTSW CONTROL
Manually Operated Control Switch, Load bank Mounted on BL0V models from 20kW to 125kw capacities only.
Typical Load Bank Model Designation BL0V…..RTSW
TYPE MC12PMB-L CONTROL
Digital Display Electronic Panel Supplied Loose For Remote Mounting And Control. Supplied With All BL Series Load Banks Standard From 150kW Capacities. Can Be Supplied Also As An Option With BL0V (20kW-125kW) Units.
TYPE MC12PMB-P CONTROL
Digital Display Electronic Panel Mounting On Load Bank. Supplied With All BL Series Load banks From 150kW Capacities.
Typical Load Bank Model Designation BL2V…..MCP
Digital Communication- RS485 Modbus™ RTU Option
MB800 Modbus Interface Module & Software Added To MC12PMB Control Panel.
Typical Load Bank Model Designation BL2V…..MCMB
Engineers Submittal Specifications
For Permanent Installation To Periodically Test & Exercise Stand-By Generators & UPS Systems. Weatherproof Construction, Complete With Controls.